Parameter: Binary Outputs > Trip Config > Trip Contacts
Default Setting: <None>
Operation of the specified contacts are identified as those that are used to trip a circuit‑breaker.
Operation of any binary output assigned as a Trip Contact will trigger storage of a Fault Data
Record, actuate the Trip Alert screen (when System Config > Trip Alert = Enabled) and
initiate the CB Fail protection sequence (when enabled).
Parameter: Binary Outputs > Trip Config > Trip Triggered
Default Setting: <None>
Operation of the selected LEDs or virtual I/Os is initiated when a binary input configured as a Trip
Contact operates. This provides a logic signal from the trip signal that can be used to provide indication
that a trip has occured.
i
i
NOTE
Where the Trip Triggered is not configured then the Trip Alert and Fault Records will not be
triggered.
Device Functionality
3.5 Binary Outputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual 83
C53000-G7040-C015-1, Edition 11.2019