Building Technologies / HVAC Products CE1B3133x2-en 74 319 0560 0 a 10.10.2006
Do you want to start DHW heating?
(Only with RMH760B)
Prerequisites
The heating plant must be commissioned by the heating
engineer.
When the preconditions are met, DHW heating is ready
to be started. Select menu option Preselection and then
select operating mode
. This is the recommended
and energy-saving operating mode.
The following choices are available:
Symbol Operating mode Impact on the DHW circuit? Guide value
Automatic The DHW temperature changes according to the DHW time program,
from normal temperature to reduced temperature, or vice versa
Normal The DHW is maintained at the normal temperature 55 °C
Reduced The DHW is maintained at the reduced temperature 40 °C
Protection No DHW heating: The plant remains protected against frost however 5 °C
Path:
Main menu > DHW > DHW optg mode > Preselection