Installing the Device
2.3Connecting Power
more information, refer to the RUGGEDCOM RS8000T Configuration Manual for the
RUGGEDCOM RS8000T.
The following shows the proper relay connections.
1
Normally Closed
2
Common
3
Normally Open
Figure2.5 Failsafe Alarm Relay Wiring
2.3 Connecting Power
The RUGGEDCOM RS8000T supports a single integrated high AC/DC or low DC power
supply
IMPORTANT
• For 88-300 VDC rated equipment, an appropriately rated circuit breaker must be
installed.
• For 100-240 VAC rated equipment, an appropriately rated circuit breaker must
be installed.
• Use minimum #16 gage wiring when connecting terminal blocks.
• A circuit breaker is not required for 12, 24 or 48 VDC rated equipment.
• Power input terminals have reverse polarity protection for 12, 24 and 48 VDC
rated equipment.
• Equipment must be installed according to applicable local wiring codes and
standards.
12
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05