Applications   
3.5 Use of 3VA UL molded case circuit breakers in IT systems according to IEC 60947-2 
  3VA molded case circuit breakers with UL and IEC certification 
148  Manual, 01/2019, L1V30435333-01 
 
Use of 3VA UL molded case circuit breakers in IT systems 
according to IEC 60947-2 
3.5.1
 
The main advantage of IT systems is that they safeguard continuity of service by electrical 
installations and are therefore deployed predominantly in consumer installations where 
availability of electrical power is a priority. As a general rule, circuits are interrupted only if 
two insulation faults occur simultaneously. 
Preferred applications for IT systems are therefore: 
●  In buildings with rooms used for medical purposes 
●  For operation of mobile generators 
●  In certain industries, e.g.: 
–  in the chemical industry 
–  in the oil industry 
–  in the steel industry 
–  in mining 
 
The IT system is a low-voltage power supply network with increased failure-safety in the 
event of ground faults. In an IT system, live phases are not connected to ground. A ground 
fault does not cause system shutdown. DIN EN 60204-1 (VE 0113) therefore stipulates that 
an insulation monitoring device must be installed in order to indicate ground faults. In the 
unusual event that a fault on the load side coincides with a second fault on the line side, the 
full phase-to-phase voltage is connected across one contact of the breaker. The Siemens 
3VA UL molded case circuit breakers for line protection, with thermal-magnetic and 
electronic trip units, are suitable for use in IT systems.  
Accordingly, the molded case circuit breakers meet the requirements of standard IEC / 
DIN EN 60947-2 Annex H up to a maximum voltage (U
e, max.
) of 690 V AC. 
 
Selection criteria for 3VA UL molded case circuit breakers 
The circuit breakers are always dimensioned and selected irrespective of the system type in 
which they will be deployed.  
The circuit breaker is always selected according to the maximum potential short-circuit 
current in the IT system. The device is selected in accordance with the relevant I
cu
 values of 
the 3VA UL molded case circuit breaker. 
If the system operator takes measures to ensure that a double-phase-to-ground fault cannot 
develop on the line side or load side of the circuit breaker, the breaking capacity I
cu
 /I
cs
 
remains unchanged in IT systems. If this cannot be ensured, the values in accordance with 
the standard IEC 60947-2 Annex H apply for single-pole short circuits.