Accessories 
  4.8 Communication and system integration 
3VA molded case circuit breakers with UL and IEC certification 
Manual, 01/2019, L1V30435333-01 
331 
 
The COM800/COM100 breaker data server enables the integration of the 3VA UL molded 
case circuit breakers in: 
●  Power monitoring software powermanager 
●  Industrial automation systems 
●  Building automation systems 
●  Parameterization and breaker condition evaluation via communication link 
●  Maintenance systems 
 
The COM800/COM100 breaker data server together with the connected 3VA UL molded 
case circuit breakers with the ETUs 5-series and 8-series provides the following information 
about the power distribution system: 
●  Condition of the 3VA UL molded case circuit breaker 
●  Tripping history with time stamp, cause of trip and number of trip events for breakers with 
ETUs 5-series and 8-series 
●  Minimum and maximum values of measured variables 
●  Limit-value monitoring for measured variables in the 3VA UL molded case circuit breakers 
●  Load curves with power demands, e.g. 15-minute demands 
●  Energy values such as active energy (kWh) and reactive energy (kvarh) 
●  Power supply to connected 3VA UL molded case circuit breakers 
●  Three simultaneous communication connections via the integrated Ethernet interface 
 
Electronic trip units allow detailed setting of protection parameters from a central location. 
They record measured variables and maintenance information in order to support power and 
installation monitoring. 
The electronic trip units (ETUs) provide the following protection functions: 
●  Overload protection L ("L" = Long time) 
●  Short-time delayed short-circuit release S ("S" = Short time) for time-selective response in 
case of a short-circuit 
●  Instantaneous short-circuit release I ("I" = Instantaneous) 
●  Protection of the neutral conductor against overload and short-circuit ("N" = neutral) 
●  Protection from fault currents to ground ("G" = Ground fault).