3.4 Parameterization
7KT multimeter
36 Manual, 08/2018, 2514284149-01
3.4.7
Command menu
The command menu allows you to perform occasional operations (e.g. to reset measured
variables and counters).
After entering the password for the extended level, you can also use the command menu to
perform automatic operations which are useful for the configuration of the device.
The following functions are available in the command menu, separated according to the
required access level.
Code
Command
Access level
Description
C.01
RESET HI-LO
User lev-
el/administrator
Resets the HI and LO values of all measurements.
C.02 RESET MAX DEMAND Resets the maximum demand values for all meas-
urements.
C.03
RESET PAR.ENERGY
Resets the partial energy meters.
C.04
RESET PAR.HOURS
Resets the partial hour counters.
C.07
RESET ALARMS
Resets alarms.
C.08
RESET LIMITS
Resets limit values
C.11 RESET TOT.ENERGY
(Not with MID devices)
Administrator Resets the total and partial energy meters.
C.12
RESET TOT.HOURS
Resets the total hour counter.
C.13
SETUP TO DEFAULT
Restores all the factory settings for the device.
C.14
BACKUP SETUP
Saves a backup copy of all setup parameters.
C.15
RESTORE SETUP
Loads the settings from the backup copy.
C.16 WIRING TEST Runs the test to check whether the device is connect-
ed correctly.
You can find more information in chapter Wiring test
(Page 37).
1. Select the required command.
2. Press to execute the command.
3. Press again to execute the command.
4. Press to cancel execution of the command.
5. Press to exit the command menu.