Communication
2.2 Modbus
53SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.22 Registers 0651 to 0764, 0781 to 0782, 0787 to 0788, and 16013 to 16018: PQ
Measured Values, Maximum Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
The data are calculated within the parameterized time (for example 30 s, 1 min etc.).
Data type: Measured value
Table 2-27 Registers 0651 to 0764, 0781 to 0782, 0777 to 0788, and 16013 to 16018: PQ Measured
Values – Maximum Values
Register Type of Information Remark Unit
0651 PQ_Va_max Voltage a-N V
0653 PQ_Vb_max Voltage b-N V
0655 PQ_Vc_max Voltage c-N V
0657 PQ_Vab_max Voltage a-b V
0659 PQ_Vbc_max Voltage b-c V
0661 PQ_Vca_max Voltage c-a V
0663 PQ_Ia_max Current a A
0665 PQ_Ib_max Current b A
0667 PQ_Ic_max Current c A
0669 PQ_VN_max Voltage neutral conductor V
0671 PQ_Vavg_max Mean value of voltage (P-N) V
0673 PQ_IN_max Current neutral conductor A
0675 PQ_Iavg_max Mean value of currents A
0677 PQ_Pa_max Active power a W
0679 PQ_Pb_max Active power b W
0681 PQ_Pc_max Active power c W
0683 PQ_P_max Active power W
0685 PQ_Qa_max Reactive power a var
0687 PQ_Qb_max Reactive power b var
0689 PQ_Qc_max Reactive power c var
0691 PQ_Q_max Reactive power var
SYS_SICAM_Q100_US.book Page 53 Thursday, September 24, 2020 1:17 PM