Commissioning a project 
  5.6 Backup and restore 
Comfort Panels 
Operating Instructions, 07/2017, A5E36770603-AB 
165 
 
 
Overview 
Backup and restore  
A data backup saves the contents of the internal memory in a backup/restore file (.brf) on a 
configuration PC or on an external storage medium. The backup/restore file does not contain 
alarm logs and process value logs. These logs are saved separately on an external storage 
medium. Back up these logs manually if required. If the HMI device is integrated in a 
network, you can also back up the data on a network drive. 
The following data is backed up in the backup/restore file:  
●  Project and HMI device image 
●  User administration 
●  Recipe data 
●  License keys 
Use WinCC for backup and restore on a configuration PC.  
 
Note 
Power failure  
If a complete restore operation is interrupted due to power failure on the HMI device, the 
operating system of the HMI device may be deleted. In this case, you have to reset the HMI 
device to its factory settings. Th
e HMI device automatically switches to "bootstrapping" 
 
Compatibility conflict  
If an alarm is output on the HMI device warning of a compatibility conflict during the restor
e 