B-5
Equipment
Manual OP7, OP17
Release 04/99
Remedy:CauseMes-
sage
217,
218
Overlapping
specified/actual values.
Check configuration of actual/speci
-
fied values in the process link.
219
Hardware fault: relay or port could not be set.
Send unit for repair
.
220
Print buf
fer overflow due to overload. Printout
not possible.
Messages have been lost.
221
Print buf
fer overflow due to overload. Printout of
overflow messages not possible.
Messages have been lost.
222 W
arning: the event message buf
fer is full apart
from the specified remaining buf
fer space.
Clear the buf
fer or configure a smal
-
ler figure for the remaining buf
fer
space.
224
The event message buf
fer has overflowed.
If a printer is connected and buf
fer
overflow has been configured, the
overflow messages will automati
-
cally be printed out.
225 W
arning: the alarm message buf
fer is full apart
from the specified remaining buf
fer space.
Clear the buf
fer or configure a smal
-
ler figure for the remaining buf
fer
space.
227
The alarm message buf
fer has overflowed.
If a printer is connected and buf
fer
overflow has been configured, the
overflow messages will automati
-
cally be printed out.
229
No keyboard connected (internal keyboard with
ribbon cable).
230
The minimum value is greater than the maximum
value for variable limits.
Correct the limit settings.
231
The minimum value is equal to the maximum va
-
lue for variable scales.
Correct the scale on the OP
.
303
Fault in connection with PLC.
S5
: this error may occur when transferring lar
ge
data records. In such cases the watchdog is activa
-
ted.
Check PLC status.
S5
: set value in data word 98 to at
least 2000.
304
Illegal S5 job number or job parameters in a func
-
tion field.
305
Data block number missing.
Set up data block or change configu
-
ration.
306
Incorrect CPU specified under ”PLC –> Parame
-
ters”.
Change configuration and retransfer
.
307 ...
311
V
ariable not present on PLC
Check configuration of process link.
312
The printer is already processing a print job and
can not accept this next job at present.
W
ait until the printer is free again
and repeat the print job.
313
Information message: print job completed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic hmi op7 and is the answer not in the manual?

Siemens simatic hmi op7 Specifications

General IconGeneral
BrandSiemens
Modelsimatic hmi op7
CategoryControl Panel
LanguageEnglish

Related product manuals