EasyManua.ls Logo

Siemens SIMATIC RF300 - Communication between Communication Module, Reader (with IQ-Sense Interface) and Transponder

Siemens SIMATIC RF300
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RF300 system planning
4.1 Fundamentals of application planning
SIMATIC RF300
System Manual, Release 04/2006, J31069 D0166-U001-A2-7618
4-9
4.1.8 Communication between communication module, reader (with IQ-Sense interface)
and transponder
Communication between the communication module (IQ-Sense), RF310R reader and
transponder takes place in fixed telegram cycles. 3 cycles of approximately 3 ms are always
needed for the transfer of a read or write command. 1 or 2 bytes of user data can be
transferred with each of these commands. The acknowledgement transfer (status or read
data) takes place in 3 further cycles. The transponder must be present within the field of the
reader during the message frame cycle.
Calculation of the communication time for interference-free transfer
The communication time for fault-free data transfer is calculated as follows:
=+ tKtn
KByte
(n >1)
Calculation of the maximum amount of user data
The maximum amount of user data is calculated as follows:
t
K
Communication time between communication module, RF310R IQ-Sense reader
and transponder
t
V
Dwell time
n Amount of user data in bytes
n
max
Max. amount of user data in bytes in dynamic mode
t
Byte
Transmission time for 1 byte
K Constant (internal system time) This contains the time for power buildup on the
transponder and for command transfer
Time constants K and t
Byte
K (ms) t
Byte
(ms) Command
15 15 Read (FRAM/EEPROM area)
15 15 Write (FRAM area)
30 30 Write (EEPROM area)
The table of time constants applies to every command. If a user command consists of
several subcommands, the above t
K
formula must be applied to each subcommand.

Table of Contents

Related product manuals