RF300 system planning
4.6 EMC Directives
SIMATIC RF300
4-46 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618
Shielding for the cables
Shield the data cables and connect the shield at both ends.
Shield the analog cables and connect the shield at one end, e.g. on the drive unit.
Always apply large-area connections between the cable shields and the shielding bus at
the cabinet inlet and make the contact with clamps.
Feed the connected shield through to the module without interruption.
Use braided shields, not foil shields.
Line and signal filter
Use only line filters with metal housings
Connect the filter housing to the cabinet chassis using a large-area low-HF-impedance
connection.
Never fix the filter housing to a painted surface.
Fix the filter at the control cabinet inlet or in the direction of the source.