Instructions
9.3 PID_Temp
PID control
Function Manual, 03/2017, A5E35300227-AC
399
AllSlaveAutomaticState BOOL FALSE If this PID_Temp instance is used as master controller in a
cascade (Config.Cascade.IsMaster = TRUE), All-
SlaveAutomaticState = TRUE indicates that all slave con-
trollers are in automatic mode.
Tuning, manual mode or automatic mode of the master
controller can only be executed accurately if all slave con-
trollers are in automatic mode.
AllSlaveAutomaticState is only determined if you intercon-
nect the master controller and slave controller with the
Master and Slave parameters.
For details, see the Master parameter.
NoSlaveSubstituteSetpoint BOOL FALSE If this PID_Temp instance is used as master controller in a
cascade (Config.Cascade.IsMaster = TRUE), NoSlave-
SubstituteSetpoint = TRUE indicates that no slave control-
ler has activated its substitute setpoint.
Tuning, manual mode or automatic mode of the master
controller can only be executed accurately if no slave
controller has activated its substitute setpoint.
NoSlaveSubstituteSetpoint is only determined if you inter-
connect the master controller and slave controller with the
Master and Slave parameters.
For details, see the Master parameter.
Heat.EnableTuning BOOL TRUE Enabling of tuning for heating
Heat.EnableTuning must be set for the following tunings
(at the same time or prior to the start with Mode and
ModeActivate):
• Pretuning heating
• Pretuning heating and cooling
• Fine tuning heating
This parameter is not automatically reset by the
Cool.EnableTuning BOOL FALSE Enabling of tuning for cooling
Cool.EnableTuning must be set for the following tunings
(simultaneously with or prior to the start with Mode and
ModeActivate):
• Pretuning cooling
• Pretuning heating and cooling
• Fine tuning cooling
Only effective if the cooling output and PID parameter
switching are activated ("Config.ActivateCooling" = TRUE
and "Config.AdvancedCooling" = TRUE).
This parameter is not automatically reset by the
Config.InputPerOn BOOL TRUE If InputPerOn = TRUE, the Input_PER parameter is used
for detecting the process value. If InputPerOn = FALSE,
the Input parameter is used.