9.4 PID basic functions
PID control
464 Function Manual, 03/2017, A5E35300227-AC
9.4.3.3
Mode of operation PULSEGEN
Modes
Depending on the parameters assigned to the pulse shaper, PID controllers with a three-step
output or with a bipolar or unipolar two-step output can be configured. The following table
illustrates the setting of the switch combinations for the possible modes.
Mode
MAN_ON
STEP3_ON
ST2BI_ON
Three-step control
FALSE
TRUE
Any
Two-step control with bi-polar
Manipulating range (-100 % to 100 %)
FALSE FALSE TRUE
Two-step control with unipolar
Manipulating range (0 % to 100 %)
FALSE FALSE FALSE
Manual mode
TRUE
Any
Any
Manual mode in two/three-step control
In the manual mode (MAN_ON = TRUE), the binary outputs of the three-step or two-step
controller can be set using the signals POS_P_ON and NEG_P_ON regardless of INV.
Control
POS_P_ON
NEG_P_ON
QPOS_P
QNEG_P
Three-step control
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
TRUE
FALSE
FALSE
TRUE
FALSE
TRUE
TRUE
TRUE
FALSE
FALSE
Two-step control
FALSE
Any
FALSE
TRUE
TRUE
Any
TRUE
FALSE