EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 402

Siemens Simatic S7-1500
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions
9.3 PID_Temp
PID control
402 Function Manual, 03/2017, A5E35300227-AC
Tag
Data type
Default
Description
Config.AdvancedCooling BOOL TRUE Method for heating/cooling
Cooling factor (Config.AdvancedCooling = FALSE)
The output value calculation for cooling takes place
with the PID parameters for heating (Re-
tain.CtrlParams.Heat structure) taking into considera-
tion the configurable cooling factor Config.CoolFactor.
This method is suitable if the heating and cooling actu-
ators have a similar time response but different gains.
Pretuning and fine tuning for cooling are not available
when you select this method. You can only execute the
tuning for heating.
PID parameter switching (Config.AdvancedCooling =
TRUE)
The output value calculation for cooling takes place by
means of a separate PID parameter set (Re-
tain.CtrlParams.Cool structure).
This method is suitable if the heating and cooling actu-
ator have different time responses and different gains.
Pretuning and fine tuning for cooling are only available
when you select this method (Mode = 1 or 2,
Cool.EnableTuning = TRUE).
Config.AdvancedCooling is only calculated if the cooling
output is activated (Config.ActivateCooling = TRUE).
Config.CoolFactor REAL 1.0 Cooling factor
If Config.AdvancedCooling = FALSE, Config.CoolFactor is
considered as factor in the calculation of the output value
for cooling. This allows different gains of heating and cool-
ing actuators to be taken into account.
Config.CoolFactor is not set automatically or adjusted
during tuning. You must correctly configure Config
.CoolFactor manually with the ratio "heating actuator
gain/cooling actuator gain".
Example: Config.CoolFactor = 2.0 means that the gain of
the heating actuator is twice as high as the gain of the
cooling actuator.
Config.CoolFactor is only effective if the cooling output is
activated (Config.ActivateCooling = TRUE) and cooling
factor is selected as method for heating/cooling (Config
.AdvancedCooling = FALSE).
Config.CoolFactor > 0.0
Config.InputScaling.Upper-
PointIn
REAL 27648.0 Scaling Input_PER high
Input_PER is scaled based on the two value pairs Upper-
PointOut, UpperPointIn and LowerPointOut, LowerPointIn.
Only effective if Input_PER is used for process value de-
tection (Config.InputPerOn = TRUE).
UpperPointIn > LowerPointIn

Table of Contents

Other manuals for Siemens Simatic S7-1500

Related product manuals