EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 421

Siemens Simatic S7-1500
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions
9.3 PID_Temp
PID control
Function Manual, 03/2017, A5E35300227-AC
421
Tag
Data type
Default
Description
PIDSelfTune.TIR.State INT 0 The TIR.State tag indicates the current phase of "fine
tuning":
State = 0: Initialize fine tuning
State = 100: Calculate standard deviation for heating
State = 200: Calculate standard deviation for cooling
State = 300: Attempting to reach setpoint for heating
with two-step control using heating
State = 400: Attempting to reach setpoint for cooling
with two-step control using cooling
State = 500: Attempting to reach setpoint for heating
with PID control
State = 600: Attempting to reach setpoint for cooling
with PID control
State = 700: Calculate standard deviation for heating
State = 800: Calculate standard deviation for cooling
State = 900: Determine oscillation and calculate pa-
rameters for heating
State = 1000: Determine oscillation and calculate pa-
rameters for cooling
State = 9900: Fine tuning successful
State = 1: Fine tuning not successful
PIDSelfTune.TIR.ProcPar-
HeatOk
BOOL FALSE TRUE: The calculation of the process parameters for fine
tuning heating was successful.
This tag is set during tuning.
It must be met for calculation of the PID parameters for
heating.
PIDSelfTune.TIR.ProcPar-
CoolOk
BOOL FALSE TRUE: The calculation of the process parameters for fine
tuning cooling was successful.
This tag is set during tuning.
It must be met for calculation of the PID parameters for
cooling.

Table of Contents

Other manuals for Siemens Simatic S7-1500

Related product manuals