EasyManua.ls Logo

Siemens Simatic S7-1500 - Page 432

Siemens Simatic S7-1500
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions
9.3 PID_Temp
PID control
432 Function Manual, 03/2017, A5E35300227-AC
State / Mode
Description of operating mode
1
Requirements for pretuning heating:
Heat.EnableTuning = TRUE
Cool.EnableTuning = FALSE
The process value must not be too close to the setpoint.
|Setpoint - Input| > 0.3 * |Config.InputUpperLimit - Config.InputLowerLimit| and
|Setpoint - Input| > 0.5 * |Setpoint|
The setpoint is greater than the process value.
Setpoint > Input
Requirements for pretuning heating and cooling:
Heat.EnableTuning = TRUE·
Cool.EnableTuning = TRUE
The cooling output is activated (Config.ActivateCooling = TRUE).
The PID parameter switching is activated (Config.AdvancedCooling = TRUE).
The process value must not be too close to the setpoint.
|Setpoint - Input| > 0.3 * |Config.InputUpperLimit - Config.InputLowerLimit| and
|Setpoint - Input| > 0.5 * |Setpoint|
The setpoint is greater than the process value.
Setpoint > Input
Requirements for pretuning cooling:
Heat.EnableTuning = FALSE·
Cool.EnableTuning = TRUE·
The cooling output is activated (Config.ActivateCooling = TRUE).
The PID parameter switching is activated (Config.AdvancedCooling = TRUE).
A "pretuning heating" or "pretuning heating and cooling" has been successful (PIDSelf-
Tune.SUT.ProcParHeatOk = TRUE), if possible at the same setpoint.
The process value must be close to the setpoint.
|Setpoint - Input| < 0.05 * |Config.InputUpperLimit - Config.InputLowerLimit|

Table of Contents

Other manuals for Siemens Simatic S7-1500

Related product manuals