Using PID_Compact   
4.2 PID_Compact V2 
  PID control 
82  Function Manual, 03/2017, A5E35300227-AC 
If one or more of the following errors occur in 
, PID_Compact switches to 
"Substitute output value with error monitoring" mode and outputs the last valid output 
value: 
–  0002h: Invalid value at Input_PER parameter. 
–  0200h: Invalid value at Input parameter. 
–  0400h: Calculation of output value failed. 
–  1000h: Invalid value at Setpoint parameter. 
If an error occurs in 
, PID_Compact continues using the manual value as 
the output value. If the manual value is invalid, the substitute output value is used. If the 
manual value and substitute output value are invalid, the output value low limit is used.  
If the following error occurs during a 
, PID_Compact remains in 
active mode: 
–  0020h: Pretuning is not permitted during fine tuning. 
When any other error occurs, PID_Compact cancels the tuning and switches to the mode 
from which tuning was started. 
As soon as no errors are pending, PID_Compact returns to automatic mode. 
●  Substitute output value while error is pending 
PID_Compact outputs the substitute output value.  
If the following error occurs, PID_Compact stays in "Substitute output value with error 
monitoring" mode and outputs the output value low limit:  
–  20000h: Invalid value at SubstituteOutput tag. 
For all other errors, PID_Compact reacts as described for "Current value while error is 
pending". 
Parameters State and Mode V2 (Page 265)