Page #76 background image
Representation of analog values
C.3 Analog value representation for resistance-type transmitters / resistance thermometers
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
76 Manual, 09/2016, A5E36647959-AB
C.3.4
Thermal resistor Ni 10, 100, 120, 200, 500, 1000, LG-Ni 1000 Climatic
The following tables list the decimal and hexadecimal values (codes) of the possible
resistance thermometer ranges.
Table C- 10 Thermal resistor Ni x0 and LG-Ni 1000 Climatic (0.00500. 0.006180. 0.006720) and Ni x0 GOST Climatic
(0.006170)
Ni x0 Climatic
in °C
(1 digit =
0.01 °C)
Units
Ni x0 Climatic
in °F
(1 digit =
0.01 °F)
Units
Range
dec
hex
dec
hex
> 155.00
32767
7FFF
> 311.00
32767
7FFF
Overflow
155.00
:
130.01
15500
:
13001
3C8C
:
32C9
311.00
:
266.01
31100
:
26601
797C
:
67E9
Overshoot
range
130.00
:
-60.00
13000
:
-6000
32C8
:
E890
266.00
:
-76.00
26600
:
-7600
67E8
:
E250
Rated range
-60.01
:
-105.00
-6001
:
-10500
E88F
:
D6FC
-76.01
:
-157.00
-7601
:
-15700
E24F
:
C2AC
Undershoot
range
< - 105.00
-32768
8000
< - 157.00
-32768
8000
Underflow

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals