Expert Functions
5.2 Extending a PROFIdrive message frame
Connection of the SINAMICS S120 to the Technology CPU
140 Product Information, 09/2011, A5E00480378-04
3. Open HW Config.
4. Open the object properties for SINAMICS S120 and click "Activate" on the
"Configuration" tab.
5. Open the "Details" tab and note the assignment of the PROFIBUS I/O addresses.
Each object of the configuration has its own area that is ended with an axis disconnector.
6. To extend a message frame, an additional setpoint or actual value slot must be inserted
in front of an axis separator. This slot will be interconnected later with a parameter in
S7T Config.