EasyManua.ls Logo

Siemens SIMATIC TP700 Comfort INOX PCT

Siemens SIMATIC TP700 Comfort INOX PCT
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing and connecting the device
3.4 Wiring rules
Comfort Panels INOX PCT
28 Compact Operating Instructions, 07/2021, A5E38804191-AE
3.4 Wiring rules
Introduction
Use suitable cables when connecting the device. The table below provides the wiring rules.
Power supply
Wiring rules for ...
Power supply
Permitted cable cross-sections of solid cables (Cu)
-
-
Permitted cable cross-sections of flexible ca-
bles (Cu)
Without wire end
sleeve
1.5 mm
2
AWG
*
: 16
With end sleeve
1.5 mm
2
AWG
*
: 16
Number of wires per connection
1
Stripped length of the wires
7 to 8 mm
End sleeves according to DIN 46228
Without plastic sleeve
Design A, 7 mm long
With plastic sleeve
Design A, 7 mm long
Sheath diameter
8.5 mm
Tool
3 mm to 3.5 mm screwdriver,
conic design
Connection system
Screw terminal
Tightening torque
From 0.5 Nm to 0.6 Nm
* American Wire Gauge
Ambient and cable temperature
Note
Permissible cable temperatures
At the max. ambient temperature of the device, you must select sufficiently large wire cross
-
sections so that the permissible cable temperatures are not
exceeded.
Example:
At an ambient temperature of 50° C, a current of, for example, 0.85 A per wire and a
cross-section of 1.5 mm² Cu, a connecting cable must be rated for a temperature range of
at least 70° C.

Table of Contents

Related product manuals