Technical specifications
5.6 Information on insulation tests, protection class and degree of protection
Comfort Panels INOX PCT
Compact Operating Instructions, 07/2021, A5E38804191-AE
43
Also observe the specifications for the extended inclination and ambient temperature range;
see section "Permitted mounting positions (Page 20)".
Note
The system components connected to the HMI device, the power supply for exa
mple, must
also be suited to the respective operating conditions.
5.6 Information on insulation tests, protection class and degree of
protection
Insulation test
The insulation strength is demonstrated in the type test with the following test voltages in
accordance with IEC 61131-2:
Insulation tested with (type test)
707 V DC to other circuits / to ground
Degree of pollution and overvoltage category
The device meets the following requirements according to IEC 61131-2:2007:
Protection against foreign objects and water
The device meets the requirements according to EN 60529.
• EN 60529
• ISO 20653
• IP69
• IP66K
Type 4x (indoor use only)
Degree of protection, front
glass
• IEC62262
• IEC62262
• IK09 (center)
• IK08 (edge)
Degree of protection, on the
front, for operation in hazard-
ous areas of Zones 2 and 22
See section "Certificates and ap-
provals (Page 36)", "ATEX/IECEx
Degree of protection, rear
Protection against contact with
standard probes. There is no
protection against the ingress of
water, dust and noxious gas.