Technical specifications
5.4 Mechanical ambient conditions
Comfort Panels INOX PCT
Compact Operating Instructions, 07/2021, A5E38804191-AE
41
Emission of radio interference
The following table shows the interference emission from electromagnetic fields according to
EN 61000-6-4, measured at the following distance.
Radiated emission (emitted interference)
< 40 dB (μV/m) quasi-peak
< 47 dB (μV/m) quasi-peak
< 76 dB peak and < 56 dB average
< 80 dB peak and < 60 dB average
Emission of radio interference voltages
< 79 dB quasi-peak and < 66 dB average
< 73 dB quasi-peak and < 60 dB average
See also
EMC information in section "Notes about usage (Page 15)".
5.4 Mechanical ambient conditions
5.4.1 Storage conditions
The following information is for a device that is transported and stored in its original
packaging.
The device was tested according to IEC 60721-3-2:2018 Class 2M4 with the following
amendments and limitations:
Vibration according to IEC 60068-2-6
5 .. 8.4 Hz, deflection 3.5 mm
8.4 ... 500 Hz, acceleration 1 g
Shock according to IEC 60068-2-27
250 m/s
2
, 6 ms, 1000 shocks
5.4.2 Operating conditions
The following information applies to a device installed according to the specifications in these
operating instructions.
The device was tested based on IEC 60721-3-3:2002 Class 3M3 with the following
amendments and limitations:
Vibration according to IEC 60068-2-6
5 ... 8.4 Hz, deflection 3.5 mm
8.4 ... 200 Hz, acceleration 1 g
Shock according to IEC 60068-2-27
2
Shock pulses within the specified range can be transferred to the display but do not impact
the functionality of the device.