Fail-Safe Electronic Modules
8.3 F -Switch PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
113
Reintegration After Discrepancy Error Parameter
This parameter is used to specify when a discrepancy error is regarded as eliminated and,
thus, when the relevant input channels can be reintegrated. The following can be assigned:
"Test of 0-signal required" or
"Test of 0-signal not required"
"Test of 0-signal required"
If you assigned "Test of 0-signal required", a discrepancy error is regarded as eliminated
once a 0-signal is present again at both of the relevant input channels.
If you are using nonequivalent sensors, i.e., the "Type of sensor interconnection" is set to "2-
channel nonequivalent", a 0-signal must be present again at the channel supplying the
wanted signal.
For information about which F-module channels supply the wanted signals, refer to the
manual for the F-module you are using.
"Test of 0-signal not required"
If you assigned "Test of 0-signal not required", a discrepancy error is regarded as eliminated
once the discrepancy at the two relevant input channels disappears.
F-modules in SIMATIC S7 for which the "Reintegration after discrepancy error" parameter is
not available also exhibit this behavior.