Diagnostics
5.2 Error Diagnostics
ET 200pro Distributed I/O System - Fail-Safe Modules
38 Operating Instructions, 05/2007, A5E00394073-02
Behavior of F-Modules When a Module Failure Occurs
In the event of a fatal internal fault in the F-module resulting in failure of the
F-module, the following occur:
The connection to the backplane bus is interrupted and the fail-safe inputs and outputs
are passivated.
Diagnostics are not issued by the F-module and the standard "Module Fault" diagnostics
message is issued.
The SF LED of the relevant F-module illuminates.
Specific Information About Diagnostic Functions
All module-specific diagnostic functions, possible causes, and corrective actions are
described in
"8/16 F-DI DC24V PROFIsafe"
,
"4/8 F-DI/4 F-DO DC24V/2A PROFIsafe"
to
"F-
Switch PROFIsafe"
.
The status and diagnostic functions indicated by LEDs on the front panel of each F-module
are also presented in these sections.
Reading Out Diagnostic Functions
You can have the cause of a fault displayed in the module diagnostics in
STEP 7
(see
STEP 7 online help
).
You can read out diagnostic functions (slave diagnostics) by means of SFC 13 in the
standard user program (see
System and Standard Functions
reference manual).
See also
Diagnostic Functions of the 8/16 F-DI DC24V PROFIsafe Electronic Module (Page 81)
Diagnostic Functions of the 4/8 F-DI/4 F-DO DC24V/2A PROFIsafe Electroni
c Module
(Page 100)
Properties of the F-Switch PROFIsafe Electronic Module (Page 133)

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
Product type designationSIMATIC
CPUVaries by model
MemoryVaries by model
Input/OutputVaries by model
CommunicationVaries by model
Programming LanguageSTEP 7
Operating Temperature0°C to 60°C (varies by model)
Protection ClassIP20
CategoryProgrammable Logic Controller (PLC)

Related product manuals