EasyManua.ls Logo

Siemens SIMATIC - Page 62

Siemens SIMATIC
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fail-Safe Electronic Modules
8.1 8 /16 F-DI DC24V PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
62 Operating Instructions, 05/2007, A5E00394073-02
Reintegration After Discrepancy Error Parameter
This parameter is used to specify when a discrepancy error is regarded as eliminated and,
thus, when the relevant input channels can be reintegrated. The following can be assigned:
"Test of 0-signal required" or
"Test of 0-signal not required"
Requirements
You have assigned the following:
Evaluation of the sensors: "1oo2 evaluation"
"Test of 0-signal required"
If you assigned "Test of 0-signal required", a discrepancy error is regarded as eliminated
once a 0-signal is present again at both of the relevant input channels.
If you are using nonequivalent sensors, i.e., the "Type of sensor interconnection" is set to "2-
channel nonequivalent", a 0-signal must be present again at the channel supplying the
wanted signal.
For information about which F-module channels supply the wanted signals, refer to the
manual for the F-module you are using.
"Test of 0-signal not required"
If you assigned "Test of 0-signal not required", a discrepancy error is regarded as eliminated
once the discrepancy at the two relevant input channels disappears.
F-modules in SIMATIC S7 for which the "Reintegration after discrepancy error" parameter is
not available also exhibit this behavior.

Table of Contents

Other manuals for Siemens SIMATIC

Related product manuals