EasyManua.ls Logo

Siemens SIMATIC - Page 78

Siemens SIMATIC
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fail-Safe Electronic Modules
8.1 8 /16 F-DI DC24V PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
78 Operating Instructions, 05/2007, A5E00394073-02
Sensor supply
The sensor must be supplied internally.
Table 8-12 Use Case 2: Assignment of Sensor Supply to Inputs
8/16 F-DI DC24V PROFIsafe 4/8 F-DI/4 F-DO DC24V/2A PROFIsafe
Input channels DI 0 to DI 3: Sensor supply Vs1
Input channels DI 4 to DI 7: Sensor supply Vs2
Input channels DI 8 to DI 11: Sensor supply Vs3
Input channels DI 12 to DI 15: Sensor
supply Vs4
Input channels DI 0 to DI 3: Sensor supply Vs1
Input channels DI 4 to DI 7: Sensor supply Vs2
Wiring Diagram for Use Case 3.1 – Connecting One Two-Channel Sensor Via Two Channels
One two-channel sensor is connected via two channels to two inputs of the F-module for
each process signal (1oo2 evaluation).
The wiring is carried out at the appropriate connection module.
The figure below illustrates an example wiring diagram for channel groups 1 and 2.
8/16 F-DI
4/8 F-DI/4 F-DO
1L+ M DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 Vs1 Vs2
L+ M
S0
S1
S2
S3
1L+
Sensor contacts are mechanically coupled.
Figure 8-13 Wiring Diagram for F-DI Modules - One Two-Channel Sensor Connected Via Two
Channels, Internal Sensor Supply
Alternatively, two one-channel sensors can be connected via two channels (see Figure
"Wiring Diagram for F-DI Modules - Two One-Channel Sensors Connected Via Two
Channels, Internal Sensor Supply"
). In this case, the same process variable is measured
with mechanically separated sensors.
WARNING
In order to achieve SIL3/Category 4 with this wiring, you must install a suitably qualified
sensor, for example, in accordance with IEC 60947.

Table of Contents

Other manuals for Siemens SIMATIC

Related product manuals