EasyManuals Logo

Siemens SIMATIC Operating Instructions

Siemens SIMATIC
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
Fail-Safe Electronic Modules
8.2 4 /8 F-DI/4 F-DO DC24V/2A PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
88 Operating Instructions, 05/2007, A5E00394073-02
Switching of Grounded Loads
If the 4/8 F-DI/4 F-DO DC24V/2A PROFIsafe electronic module switches loads that have a
connection between the chassis and ground (e.g., to improve the EMC properties) and if the
chassis and ground are connected in the power supply, a "short circuit" will be detected.
From the perspective of the F-module, the M-switch (current sinking) is bridged by the
chassis-ground connection (refer to the following figure for an example for a 4/8 F-DI/4 F-DO
DC24V/2A PROFIsafe electronic module).
Remedy:
The resistance (R) between the chassis and ground on the load side must be greater than
100 kΩ.
/
/
0
0
b)',)'2'&9$352),VDIH
0
5
3VZLWFK
FXUUHQWVRXUFLQJ
5HDGEDFNRIFXUUHQWVRXUFH
RXWSXW
&HQWUDO
JURXQGLQJ
SRLQW
0VZLWFK
FXUUHQWVLQNLQJ
/RDG
5HDGEDFNRIFXUUHQWVLQN
RXWSXW
Figure 8-15 Switching Grounded Loads (Resistance Between Chassis and Ground)

Table of Contents

Other manuals for Siemens SIMATIC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC and is the answer not in the manual?

Siemens SIMATIC Specifications

General IconGeneral
Product type designationSIMATIC
CPUVaries by model
MemoryVaries by model
Input/OutputVaries by model
CommunicationVaries by model
Programming LanguageSTEP 7
Operating Temperature0°C to 60°C (varies by model)
Protection ClassIP20
CategoryProgrammable Logic Controller (PLC)

Related product manuals