04/96
Siemens AG 2001 All rights reserved 6FC5198jAB40
1–220
SINUMERIK 840C / SIMODRIVE 611D (DA)
300907 Tolerance for safe operational stop exceeded POWER ON
Cyclic in SI monitoring cycle.
The drive is stopped with STOP A or STOP B. The pulses are disabled via relay Drive_IMP”.
The actual position has migrated too far from the set/standstill position (outside the standstill window). The stand-
still window is configured in MD 1330.
The user must find the cause and initiate appropriate measures.
Applies as from SW 5.4
300908 Stop C triggered Reset key
Cyclic in SI monitoring cycle.
The drive is stopped with STOP C. After completion of the stop reaction, the drive remains under control, and the
axis is monitored for SBH.
There can be several reasons for triggering STOP C (depending on the configuration):
S The safe speed monitoring has responded (MD 1361).
S The safe end position monitoring has responded (MD 1362).
The user must find the cause and initiate appropriate measures.
Applies as from SW 5.4
300909 Stop D triggered Reset key
Cyclic in SI monitoring cycle.
The NC has stopped the drive with STOP D. After completion of the stop reaction, the drive remains under control,
and the axis is monitored for SBH.
There can be several reasons for triggering STOP D (depending on the configuration):
S The safe speed monitoring has responded (MD 1361).
S The safe end position monitoring has responded (MD 1362).
The user must find the cause and initiate appropriate measures.
Applies as from SW 5.4
300910 Stop E triggered Reset key
Cyclic in SI monitoring cycle.
The NC has stopped the drive with STOP E. After completion of the stop reaction, the drive remains under control,
and the axis is monitored for SBH.
There can be several reasons for triggering STOP E (depending on the configuration):
S The safe speed monitoring has responded (MD 1361).
S The safe end position monitoring has responded (MD 1362).
The user must find the cause and initiate appropriate measures.
Applies as from SW 5.4
300911 Failure in a monitoring channel Reset key
Cyclic in SI monitoring cycle.
If no Safety Integrated monitoring system is active, STOP F does not initiate a stop response, but displays the
message Failure in a monitoring channel”.
If SBH/SG, SE or SN are active, the drive is stopped with the stop response STOP A/B.
Crosscomparison between NC and drive has revealed a difference, and STOP F has been initiated.
Find the difference between the monitoring channels. The error code which indicates the cause appears
as follows:
S on 840C
MD 301: Diagnostics for STOP F
S on 611D
MD 1395
The meaning of the error code can be found in the SINUMERIK Safety Integrated documentation.
It is possible that the safetyrelated machine data are no longer identical or that the SGEs do not have the same
signal level (measure again or check in the SI service display). If no such error is found, an error may have oc-
curred in the CPU, such as a corrupt memory cell. This error can be transient (remedied by POWER ON) or per-
manent (reoccurs after POWER ON, in this case replace the hardware).
Applies as from SW 5.4
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
1 Alarms
1.5.1 Alarm description
07/97

Table of Contents

Other manuals for Siemens SIMODRIVE 611-D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMODRIVE 611-D and is the answer not in the manual?

Siemens SIMODRIVE 611-D Specifications

General IconGeneral
BrandSiemens
ModelSIMODRIVE 611-D
CategoryControl Unit
LanguageEnglish

Related product manuals