07.94
1-107
Siemens AG 1997 All Rights reserved
SIMODRIVE 611A Installation and Start–Up Guide/IAA/–04.97 Edition
Setting elements with user–friendly interface
Setting elements on the parameter board; terminal = H jumpered
with terminal 9, terminal = L open.
Function Component(s) Effect
Ready/fault
Relay terminal 672/673/674
R33 = 0 (as supplied)
R33 = open
Ready signal
fault signal
Speed/current controlled
(permanently selected via switch)
S2: 10 = OFF (as supplied)
S2: 10 = ON
Closed–loop speed control
closed–loop current control
Speed/current controlled
(selected via terminal)
R14 = 0
1)
; terminal 22 = L
R14 = 0 ; terminal 22 = H
Closed–loop speed control
closed–loop current control
Supplementary setpoint 1 via terminal
22 = H
R16 (as supplied = open)
2)
R17 (as supplied = open)
R18 (as supplied = open)
Voltage divider at 10 V
Voltage divider at –10 V
Voltage divider at the ref. point
Supplementary setpoint 2 via terminal
23 = H
R21 (as supplied = open)
2)
R19 (as supplied = open)
R22 (as supplied = open)
Voltage divider at 10 V
Voltage divider at –10 V
Voltage divider at the ref. point
Current–controlled operation with/
without I component
R1 = 0 (as supplied)
R1 = open
I component inhibited P
I component active PI
Controller– and pulse inhibit via
terminal 65
R13 = open (as supplied)
R13 = 0
Delayed
Instantaneous
Master-/slave operation:Master opera-
tion
R42 + R44 = 0 , S2: 10 = OFF Master operation, terminal 258 = out-
put
Slave operation
R44 = 0 , R1 + R42 = open,
S2: 10 = ON
Slave operation, terminal 258 = input
Timer, speed controller at its endstop
R54 = 360 k (as supplied)
R54 as selected
t = 230 ms
t [ms]
R54 [kΩ] =
0.56
– 47
Monitoring, n controller at n stop
R32 = 0 (as supplied)
R32 = open
Monitoring active
Monitoring inactive
Direction of rotation reversal
(direction of rotation for a positive set-
point at terminal 56/14)
S2: 1 = ON (as supplied)
S2: 1 = OFF
Motor ccw, drive shaft end
Motor cw, drive shaft end
Speed controller smoothing C3 (as supplied = open) τ = C3 68 k
Speed setpoint smoothing C4 (as supplied = open) τ = C4 10 k
Speed actual value smoothing C5 (as supplied = open) τ = C5 5 k
Current setpoint smoothing C6 (as supplied = open) τ = C6 1 k
Speed setpoint adaptation
2)
(only terminal 56/14)
R5 = 20 k (as supplied)
|100% n
ACTN
|=11 ... 5V
Current setpoint adaptation R42 (as supplied = 0 )
2)
I
set
10 V
Travel to endstop
(set using R12)
R12 according to Fig. 3–3
Condition: Terminal 96 connected to
terminal 44
Limiting according to Fig. 3–3
Speed controller monitoring inactive
1)As supplied: R14 = open
N
set
10V
2)R=
40k
N
rated
N
max
()
0.5
Feed modules (VS)
04.97 3.2 Setting elements with user–friendly interface