All of the specified outputs are valid up to an installation altitude of 1000 m. For
an installation altitude > 1000 m, the specified outputs should be reduced ac-
cording to the diagrams below. For installation altitudes > 2000 m
1)
an isolating
transformer must be used (refer to Section 2.4).
100 %
0
1000
2000
Installation altitude (m)
80 %
60 %
40 %
20 %
0 %
3000 4000 5000
X
H
P
n
altitude
=x
H
P
n1000m
/100%
P
n
altitude
=x
H
P
s61000m
/100%
P
max.
altitude
=x
H
P
max.
1000m
/100%
Figure 3-3
Caution: P
n
, P
s6
and P
max
must be de–rated in the same way.
Table 3-5 UE modules with pulsed resistors
Pulsed resistors, technical data
External pulsed
resistor 0.3/25
kW
External pulsed
resistor 1.5/25
kW
Internal pulsed
resistor 0.3/25
kW
Internal pulsed
resistor 0.2/10
kW
Order No.,
pulsed re-
sistor
6SN1113–
1AA00–0DA0
6SN1113–
1AA00–0CA0
– –
Integrated
in
– – UE 10 kW,
pulsed resistor
module
UE 5 kW
Can be
used for
UE module 28
kW
UE module 28
kW
– –
Can be
used for
–
Pulsed resistor
module
6SN1113–
1AB0–0BA
– –
Pn 0.3 kW 1.5 kW 0.3 kW 0.2 kW
P
max
25 kW 25 kW 25 kW 10 kW
E
max
7.5 kWs 180 kWs 7.5 kWs 13.5 kWs
Degree of
protection
IP 54 IP20 refer to module refer to module
Dimension drawings, refer to p. 1-161
1)
The rated insulation voltage depends on the installation altitude.
De–rating as a
function of the in-
stallation altitude
3.2.1 Technical data, supply infeed modules