Connecting the SIMODRIVE 611U to the Technology CPU
Product Information, 03/2008, A5E00272066-05
9
Software Requirements
3
3.1 Converter
3.1.1 Software upgrade
Note
The SimoCom U must not be connected using PROFIBUS DP when the software upgrade is
performed!
Procedure
1. Connect SimoCom U to the drive via the V24 interface.
2. Open the firmware download window.
If you want to upgrade the drive yourself, select the menu command Options > Service >
Firmware upgrade. If you want to upgrade the PROFIBUS module, select the menu
command Options > Service > Firmware upgrade of PROFIBUS option module.