Commissioning
4.5 Drive configuration for SIMODRIVE 611U
Connecting the SIMODRIVE 611U to the Technology CPU
Product Information, 03/2008, A5E00272066-05
61
4.5 Drive configuration for SIMODRIVE 611U
Procedure
The SimoCom U commissioning tool is used for commissioning the SIMODRIVE 611U. This
SimoCom U commissioning tool is intuitive for the most part. You are guided through the
individual steps.
The connection to the drive can either be made via a serial interface or PROFIBUS DP.
First, the drive configuration prompting is used to configure the hardware (associated power
section, motors, encoders, etc.), the PROFIBUS interfaces, etc.
Once you have started SimoCom U, you will be prompted in the first window where you
want to change the data for the drive.
Establish a connection (serial, PROFIBUS DP) between SimoCom U and the drive and
select "Find online drives...". This has the advantage that you do not need to enter the
data for the closed-loop control card and the PROFIBUS module. This data is read out
and displayed by SimoCom U.
Note
To allow you to operate the SIMODRIVE 611U PROFIDrive-conform, the following
parameters have been added or extended with the software version from 06.02.2003:
P1012.2 → must be set
P1012.12 → must be set
P1012.13 → must be set
P1012.14 → may not be set
The help for P878 provides further information.