03.2004 Start-up
Siemens AG 6SE7087-7CX87-2DA0
SIMOVERT MASTERDRIVES Unité de Freinage / Braking Unit 6-3
6.1 Capacitor forming
The DC link capacitors must be re-formed if the converter has been
non-operational for more than one year. If the converter was started-up
within one year after having been shipped (serial number on the rating
plate), it is not necessary to re-form the DC link capacitors.
Forming is realized by switching-in a rectifier and resistor, which is
connected to the DC link. The converter supply must be
disconnected!
(circuit: refer to Fig. 6-1.)
The forming time is dependent on the time during which the converter
was not operational (see Fig. 6-2).
Position Example Significance / Example
7 A
B
C
Manufacturing year: 2000
2001
2002
8 and 9 06 Manufacturing month: 06
10 and 11 04 Manufacturing day: 04
12 to 14 Not relevant for forming (serial
number)
Table 6-2 Serial number structure: NW903160604095