Installing
3.1 Mounting
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
15
Mounting on a control cabinet panel
Table 3- 2 Drilling templates and mounting equipment, FSD … FSF
Frame size D
22 kW … 45 kW
Frame size E
55 kW
Frame size F
75 kW … 132 kW
Drilling pattern
Mounting parts 4 x M5 bolts
4 x M5 nuts
4 x M5 washers
4 x M6 bolts
4 x M6 nuts
4 x M6 washers
4 x M8 bolts
4 x M8 nuts
4 x M8 washers
Locked-rotor
(starting) torque
6 Nm 10 Nm 25 Nm
Protection against the spread of fire
The device may be operated only in closed housings or in control cabinets with protective
covers that are closed, and when all of the protective devices are used. The installation of
the device in a metal control cabinet or the protection with another equivalent measure must
prevent the spread of fire and emissions outside the control cabinet.
Protection against condensation or electrically conductive contamination
Protect the device, e.g. by installing it in a control cabinet with degree of protection IP54
according to IEC 60529 or NEMA 12. Further measures may be necessary for particularly
critical operating conditions.
If condensation or conductive pollution can be excluded at the installation site, a lower
degree of control cabinet protection may be permitted.