Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
32 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
3.2.7
Default setting of the interfaces
The function of the terminals and fieldbus interface can be set.
In order that you do not have to successively change terminal for terminal, several terminals
can be jointly set using default settings ("p0015 Macro drive unit").
The factory setting of the terminals described above corresponds to the default setting 7
(p0015 = 7): "Fieldbus with data set switchover".
Default setting 1: "Conveyor technology with 2 fixed frequencies"
DO 0: p0730, DO 1: p0731
AO 0: p0771[0]
DI 0: r0722.0, …, DI 5: r0722.5
Fixed speed setpoint 3: p1003, fixed speed setpoint 4: p1004, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
DI 4 and DI 5 = high: the inverter adds the two fixed speed setpoints
Designation in the BOP-2: coN 2 SP
Default setting 2: "Conveyor system with Basic Safety"
DO 0: p0730, DO 1: p0731
AO 0: p0771[0]
DI 0: r0722.0, …, DI 5: r0722.5
Fixed speed setpoint 1: p1001, fixed speed setpoint 2: p1002, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
DI 0 and DI 1 = high: the inverter adds the two fixed speed setpoints.
Designation in the BOP-2: coN SAFE