Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
33
Default setting 3: "Conveyor system with 4 fixed frequencies"
DO 0: p0730, DO 1: p0731
AO 0: p0771[0]
DI 0: r0722.0, …, DI 5: r0722.5
Fixed speed setpoint 1: p1001, … fixed speed setpoint 4: p1004, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
Several of the DI 0, DI 1, DI 4, and DI 5 = high: the inverter adds the corresponding fixed speed set-
points.
Designation in the BOP-2: coN 4 SP
Default setting 4: "Conveyor system with fieldbus"
DO 0: p0730, DO 1: p0731
AO 0: p0771[0]
Speed setpoint (main setpoint): p1070[0] = 2050[1]
Designation in the BOP-2: coN Fb