SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
79
Troubleshooting and additional information
5
5.1
List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 5- 1 The most important alarms and faults
Number
Cause
Remedy
F01000 Internal software error Replace the inverter.
F01001
FloatingPoint exception
Switch off the inverter and switch on again
F01015
Internal software error
Upgrade firmware or contact technical support.
F01018 Power-up aborted more than
once
1. Switch off the inverter power supply and switch it on again.
2. After this fault, the inverter powers up with the factory settings.
3. Recommission the inverter.
A01028 Configuration error Explanation: The parameter assignments on the memory card were made
with a different type of module (article no.).
Check the module parameters and recommission if necessary.
F01033 Unit switchover: Reference pa-
rameter value invalid
Set the value of the reference parameter to a value other than 0.0 (p0304,
p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).
F01034 Unit switchover: Calculation of
the parameter values after refer-
ence value change unsuccessful
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
F01040 Parameters must be saved Backup parameter (p0971).
Switch off the inverter and switch on again.
F01044 Loading memory data card de-
fective
Replace the memory card or the inverter.
F01105
CU: Insufficient memory
Reduce number of data sets.
F01122 Frequency at the probe input too
high
Reduce the frequency of the pulses at the probe input.
F01205
CU: Time slice overflow
Contact technical support.
F01250
CU hardware fault
Replace the inverter.
F01512 An attempt has been made to
establish a conversion factor for
scaling which does not exist
Create scaling or check transfer value.
A01590 Motor maintenance interval
elapsed
Carry out the maintenance.
F01600
STOP A initiated
Select STO and then deselect again.
F01650 Acceptance test required Carry out an acceptance test and create test certificate.
Switch off the Control Unit and switch on again.