Troubleshooting and additional information
5.1 List of alarms and faults
SINAMICS G120C, FSD ... FSF inverters
80 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
F01659 Write task for parameter rejected Cause: The inverter should be reset to the factory setting. However, it is not
permissible to reset the safety functions as the safety functions are currently
Remedy with operator panel:
Enter password for the safety functions.
p0970 = 5 Reset start safety parameter.
The inverter sets p0970 = 5 once it has reset the pa-
Then reset the inverter to the factory setting again.
F01662 CU hardware fault Switch off the inverter and switch on again, upgrade the firmware or contact
A01666 Static 1 signal at the F-DI for
Set F-DI to a logical 0 signal.
A01698 Commissioning mode active for
This message is withdrawn after the Safety commissioning has ended.
A01699 Switch-off signal path test re-
After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset
F03505 Analog input, wire break Check the connection to the signal source for interrupts.
Check the level of the signal supplied.
The input current measured by the analog input can be read out in r0752.
A03520 Temperature sensor fault Check that the sensor is connected correctly.
A05000
A05001
A05002
A05004
Power Module overtemperature Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
F06310 Supply voltage (p0210) incor-
rectly parameterized
Check the parameterized supply voltage and if required change (p0210).
F07011 Motor overtemperature Reduce the motor load.
Check ambient temperature.
Check sensor's wiring and connection.
A07012 I2t motor model overtemperature Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
A07015 Motor temperature sensor alarm Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
F07016 Motor temperature sensor fault Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Unit switchover: Parameter limit
Check the adapted parameter values and if required correct.