Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
30 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
→ If you also wish to use the power supply at terminals 31, 32 for the digital inputs, then you
must connect "DI COM1/2" and "GND IN" with one another.
For the analog input, you can use the internal 10 V supply or an external voltage source.
→ if you use the internal 10 V power supply, you must connect AI 0- or AI 1- to GND.
Further wiring options for digital inputs
Connection of contacts switching to P potential with an
external power source
If you want to connect the potential
of the external power source to the
potential of the inverter’s internal
power supply, you must connect
"GND" to terminals 34 and 69.
Connection of contacts switching to N potential with an
external power source
Connect terminals 69 and 34 to each
other.