Installing
3.2 Connecting
SINAMICS G120C, FSD ... FSF inverters
38 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
Default setting 15: "Process industry"
AO 0: p0771[0] DI 0: r0722.0, …, DI 5: r0722.5 AI 0: r0755[0]
Motorized potentiometer, setpoint after the ramp-function generator: r1050
Speed setpoint (main setpoint): p1070[0] = 755[0], p1070[1] = 1050
Designation in the BOP-2: Proc
Default setting 17: "2-wire (forw/backw1)"
AO 0: p0771[0] DI 0: r0722.0, …, DI 2: r0722.2 AI 0: r0755[0]
Speed setpoint (main setpoint): p1070[0] = 755[0]
Designation in the BOP-2: 2-wIrE 1