Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C, FSD ... FSF inverters
46 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
Motor cooling:
SELF: Natural cooling
FORCED: Forced-air cooling
LIQUID: Liquid cooling
NO FAN: Without fan
Select the basic setting for the motor control:
VEC STD: Constant load; typical applications include conveyor drives
PUMP FAN: Speed-dependent load; typical applications include pumps and fans
Select the default setting for the interfaces of the inverter that is suitable for your application.
Default setting of the interfaces (Page 32)
Minimum and maximum motor speed
Ramp-up and ramp-down time of the motor
Ramp-down time after the OFF3 command
Motor data identification Select the method which the inverter uses to measure the data of
the connected motor:
OFF: No motor data identification
STILL: Measure the motor data at standstill. The inverter switches off the motor after the
motor data identification has been completed.
Complete quick commissioning as follows:
1. Switchover the display using an arrow key: nO YES
2. Press the OK key.
You have completed quick commissioning.