Commissioning
4.2 Commissioning with BOP-2 operator panel
SINAMICS G120C, FSD ... FSF inverters
48 Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
Motor cooling:
● SELF: Natural cooling
● FORCED: Forced-air cooling
● LIQUID: Liquid cooling
● NO FAN: Without fan
Select the basic setting for the motor control:
● OP LOOP: Recommended setting for standard applications
● CL LOOP: Recommended setting for applications with short ramp-up and ramp-down
times. This setting is not suitable for hoisting gear and cranes/lifting gear.
● HVY LOAD: Recommended setting for applications with a high break loose torque.
Select the default setting for the interfaces of the inverter that is suitable for your application.
Default setting of the interfaces (Page 32)
Minimum and maximum motor speed
Ramp-up and ramp-down time of the motor
Ramp-down time after the OFF3 command
Motor data identification: Select the method which the inverter uses to measure the data of
the connected motor:
● OFF: Motor data is not measured.
STIL ROT: Recommended setting: Measure the motor data at standstill and with the
motor rotating.
The inverter switches off the motor after the motor data identification has been
completed.
● STILL: Measure the motor data at standstill.
The inverter switches off the motor after the motor data identification has been
completed.
Select this setting if the motor cannot rotate freely – for example, if the traversing range is
mechanically limited.