Installation
3.8 Connecting the PROFINET interface
Getting Started
Getting Started, FW V4.5, A5E03404762A AB
41
Setting the PROFIBUS DP address via DIP switches
The PROFIBUS DP address can be set via DIP switch, as shown in the table below.
Table 3- 11 Example address for the PROFIBUS DP interface
DIP switch 1 2 3 4 5 6 7
Add to address 1 2 4 8 16 32 64
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
3.8 Connecting the PROFINET interface
Industrial Ethernet Cables and cable length
Listed in the table below are the recommended Ethernet cables.
Table 3- 12 Recommended PROFINET cables
Max. Cable Length Order Number
Industrial Ethernet FC TP
Standard Cable GP 2 x 2
100 m (328 ft) 6XV1840-2AH10
Industrial Ethernet FC TP
Flexible Cable GP 2 x 2
85 m (278 ft) 6XV1870–2B
Industrial Ethernet FC Trailing
Cable GP 2 x 2
85 m (278 ft) 6XV1870–2D
Industrial Ethernet FC Trailing
Cable 2 x 2
85 m (278 ft) 6XV1840–3AH10
Industrial Ethernet FC Marine
Cable 2 x 2
85 m (278 ft) 6XV1840–4AH10
Cable screening
The screen of the PROFINET cable must be connected with the protective earth. The solid
copper core must not be scored when the insulation is removed from the core ends.