Getting Started
Getting Started, FW V4.5, A5E03404762A AB
55
Troubleshooting
5
5.1 List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 5- 1 The most important alarms and faults of the safety functions
Number Cause Remedy
F01600 STOP A Triggered STO Select and then deselect again.
F01650 Acceptance test required Carry out acceptance test and create test certificate.
Switch the Control Unit off and then on again.
Cause: The converter should be reset to the factory setting. The resetting of
the safety functions is, however, not allowed, because the safety functions
are currently enabled.
Remedy with operator panel:
p0010 = 30 Parameter reset
p9761 = … Enter password for the safety functions.
p0970 = 5 Reset Start Safety Parameter.
The converter sets p0970 = 5 if it has reset the parameters.
F01659 Write task for parameter rejected
Then reset the converter to the factory setting again.
A01666 Static 1 signal atF-DI for safe
acknowledgment
F-DI to a logical 0 signal.
A01698 Commissioning mode active for
safety functions
This message is withdrawn after the Safety commissioning has ended.
A01699 Shutdown path test required After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
F30600 STOP A Triggered STO Select and then deselect again.
Table 5- 2 The most important alarms and faults
Number Cause Remedy
F01018 Power-up aborted more than
once
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the converter.
A01028 Configuration error Explanation: Parameterization on the memory card has been created with a
different type of module (order number, MLFB)
Check the module parameters and recommission if necessary.
F01033 Unit switchover: Reference
parameter value invalid
Set the value of the reference parameter to a value other than 0.0 (p0304,
p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).