Commissioning
4.4 Reset Parameters to Factory Settings
Getting Started
54 Getting Started, FW V4.5, A5E03404762A AB
For further information, refer to the section "Factory Settings of the Control Unit" in this
manual.
Note
When resetting the parameters to the factory setting, the communications memory is re-
initialized. This means that communications are interrupted for the time it takes to perform
the reset.
WARNING
Parameter reset in case of CUs with fail-safe functions
Parameters that don't relate to fail-safe functions are reset with P0970 = 1.
To reset parameters that relate to fail-safe functions an additional parameter reset with
P0970 = 5 must be performed. This parameter reset is password protected.
In case of a parameter reset with P0970 = 5 an acceptance test necessary.