Installing
3.5 Default setting of the interfaces
CU230P-2 Control Units
32 Compact Operating Instructions, 01/2017, A5E38815802B AA
Default setting 114: "P1 fieldbus"
DO 0: p0730, …, DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1]
DI 2: r0722.2
Designation in the BOP-2: p_f_P1
Default setting 120: "PID settings for pumps and fans"
The default setting restores the function of the terminal strip to the factory setting.
Technology controller setting:
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
Ramp-up/down time for controller output: p2293 = 30 s
Actual value upper limit: p2267 = 120%
Actual value filter time constant: p2265 = 10 s
Designation in the BOP-2: P_F_PID