Installing
3.5 Default setting of the interfaces
CU230P-2 Control Units
Compact Operating Instructions, 01/2017, A5E38815802B AA
31
Default setting 113: "Temperature-dependent pressure setpoint"
DO 0: p0730, …,
DO 2: p0732
AO 0: p0771[0], AO 1: p0771[1] DI 0: r0722.0 AI 0: r0755[0], AI 2: r0755[2]
Additional settings:
Temperature control using the technology controller
Technological unit: p0595 = 1 (%), reference variable: p0596 = 1
Default setting of the technology controller:
Enable: p2200 = 1
Upper and lower limits, setpoint: p20229 = 0.5 , p20230 = 0.2
Ramp-up/down time for setpoint: p2257 = p2258 = 30 s
Ramp-up/down time for controller output: p2293 = 30 s
Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 %
Actual value filter time constant: p2265 = 10 s
Technology controller minimum limiting p2292 = 20 %
"Flying restart" is enabled: p1200 = 1
Automatic restart is active. After a power failure, the inverter automatically acknowledges possible
faults and switches on the motor: p1210 = 26
Designation in the BOP-2: P_F_tP5