Installing 
  3.5 Default setting of the interfaces 
CU230P-2 Control Units 
Compact Operating Instructions, 01/2017, A5E38815802B AA 
31 
AO 0: p0771[0], AO 1: p0771[1]  DI 0: r0722.0  AI 0: r0755[0], AI 2: r0755[2] 
Additional settings: 
•  Temperature control using the technology controller 
•  Technological unit: p0595 = 1 (%), reference variable: p0596 = 1 
•  Default setting of the technology controller: 
–  Enable: p2200 = 1 
–  Upper and lower limits, setpoint: p20229 = 0.5 , p20230 = 0.2 
–  Ramp-up/down time for setpoint: p2257 = p2258 = 30 s 
–  Ramp-up/down time for controller output: p2293 = 30 s 
–  Upper and lower limits, actual value: p2267 = 120 %, p2268 = -10 % 
–  Actual value filter time constant: p2265 = 10 s 
–  Technology controller minimum limiting p2292 = 20 % 
•  "Flying restart" is enabled: p1200 = 1 
•  Automatic restart is active. After a power failure, the inverter automatically acknowledges possible 
faults and switches on the motor: p1210 = 26