Commissioning
4.4 Frequently required parameters
CU230P-2 Control Units
Compact Operating Instructions, 01/2017, A5E38815802B AA
47
Analog inputs actual value [%]
[2] Terminals 50, 51 AI 2
0: Unipolar voltage input (0 V …+10 V)
1: Unipolar voltage input monitored (+2 V... +10 V)
2: Unipolar current input (0 mA …+20 mA)
3: Unipolar current input monitored (+4 mA …+20 mA)
4: Bipolar voltage input (-10 V …+10 V)
6: LG-Ni1000 temperature sensor
7: PT1000 temperature sensor
8: No sensor connected
10: Temperature sensor DIN Ni 1k (6180 ppm / K)
Analog outputs signal source
Selection of the possible settings:
0: Analog output locked
21: Speed actual value
24: Output frequency, smoothed
25: Output voltage, smoothed
26: DC-link voltage smoothed
27: Actual current value (smoothed
[1] Terminals 26, 27 AO 1
0: Current output (0 mA … +20 mA)
1: Voltage output (0 V … +10 V)
2: Current output (+4 mA ... +20 mA)
PROFIdrive telegram selection
Selection of the possible settings:
0: Main setpoint = 0
755[0]: Analog input 0
1050: Motorized potentiometer
2050[1]: PZD 2 from the fieldbus
Ramp-function generator ramp-up time [s]
Ramp-function generator ramp-down time [s]
Open-loop/closed-
loop control operat-
ing mode
Selection of the possible settings:
0: U/f control with linear characteristic
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic charac-
teristic
20: Speed control (without encoder)
Starting (voltage boost) permanent