Connection
5.1 Line and motor connection
PM250 Power Module
Hardware Installation Manual, 01/2016, A5E36265179B-AA
29
Line and motor connection
Note:
Arrangement of the line and motor terminals (Page 36).
EMC-compliant installation (Page 38).
The machine manufacturer must ensure that in operation the voltage drop between the
transformer input terminals and the inverter when operated with its rated values is less than
1%.
Permissible line supplies
Note
Restrictions for installation altitudes above 2000 m
Above an installation altitude of 2000
m, the permissible line supplies are restricted.
Restrictions for special ambient conditions (Page 61).
The inverter is designed for the following power distribution systems according to IEC 60364-
1 (2005).