Connection
5.1 Line and motor connection
PM250 Power Module
32 Hardware Installation Manual, 01/2016, A5E36265179B-AA
IT system
In an IT line system, all of the conductors are insulated with respect to the PE protective
conductor or connected to the PE protective conductor through an impedance.
There are IT line supplies where the neutral conductor N is either transferred or not.
Inverter operated on an IT line system
Inverters with integrated line filter:
Operation on IT line systems not permissible.
Inverter without line filter:
Operation on all IT line systems permissible.
Example of a Power Module connected to an IT line system
Image 5-3 IT line supply where the neutral conductor N is transferred and with impedance with
respect to the PE protective conductor
Behavior of the inverter when a ground fault occurs
In some instances, even for a ground fault, the inverter should still remain functional. In
cases such as these, you must install an output reactor. This prevents an overcurrent trip or
damage to the drive.
5.1.2
Dimensioning the protective conductor
WARNING
Danger to life caused by high leakage currents for an interrupted protective conductor
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
Lay the protective conductor as specified.